COAL FINENESS & FLY ASH LOI
LABORATORY TESTING SERVICES
Coal & Fly Ash Analysis: On-Site or In Our Advanced Labs
Accurate Fuel Analysis. Reliable Combustion Data. Better Boiler Performance Decisions.
SAS Global Corporation provides comprehensive Coal Fineness and Fly Ash Analysis Services for coal-fired electric power generation facilities seeking to evaluate pulverizer performance, fuel preparation, combustion burnout, and boiler operating conditions.
Properly ground pulverized coal is essential to efficient fuel delivery and combustion. Excessively coarse coal particles, improper classification, and uneven fuel distribution can contribute to incomplete combustion, elevated fly ash Loss on Ignition (LOI), increased maintenance concerns, and reduced boiler performance.
SAS Global combines on-site mobile combustion laboratories with its Combustion Analysis Laboratory to provide detailed coal particle-size analysis and fly ash LOI testing.
Pulverized Coal Fineness Testing
Coal fineness testing determines the particle-size distribution of pulverized fuel delivered by the coal mill or pulverizer.
By evaluating material passing or retained on specified sieves, SAS Global helps plant engineers assess grinding and classification performance and determine whether pulverized coal meets the applicable equipment or performance specification.
These measurements can support evaluations of classifier adjustments, grinding component condition, pulverizer capacity, and fuel preparation.
Fly Ash Loss on Ignition (LOI) Analysis
SAS Global provides fly ash LOI testing to evaluate the mass loss of combustion residue during a defined analytical heating procedure. LOI is commonly used as an indicator of residual combustible material and can provide useful information when assessing coal combustion burnout. Results are interpreted alongside coal fineness, boiler operating conditions, and other combustion measurements.
Composite and Particle-Size-Based LOI Testing
In addition to composite fly ash LOI analysis, SAS Global offers analysis of the fraction passing 200 mesh.
Separating and evaluating selected particle-size fractions can provide additional information about how the ash's mass-loss characteristics vary with particle size.
This information can support more detailed investigations into combustion residue behavior and possible causes of elevated LOI.
Mobile & Laboratory Testing Capabilities
Our mobile laboratories support field-testing programs where timely coal fineness and fly ash results can assist plant personnel during diagnostic evaluations. Our Combustion Analysis Laboratory supports submitted samples, specialized testing programs, and more detailed analytical evaluations.
Connecting Laboratory Results to Coal Mill Performance
Coal fineness and fly ash LOI are most useful when interpreted alongside the complete combustion process.
SAS Global can combine laboratory results with ACFM Extractive Fuel Pipe Testing, furnace temperature mapping, multi-stream flue gas analysis, and combustion tuning evaluations.
This integrated approach helps engineers investigate whether changes in pulverizer performance, fuel distribution, burner operation, or combustion conditions are contributing to plant performance problems.
Engineering Support Beyond Laboratory Testing
SAS Global combines laboratory diagnostics with extensive experience in coal pulverizer modernization, patented fuel-distribution technologies, burner components, engineering, and field services. Laboratory testing establishes measurable information. Engineering recommendations and approved corrective work can then be evaluated through follow-up testing.
Key Features
- ASTM-Compliant Procedures – All fineness testing follows ASTM D197-87, the recognized Standard Test Method for Fineness of Pulverized Coal.
- Double Testing for Accuracy – We conduct two independent tests on each sample to ensure results are both repeatable and reliable.
- Climate-Controlled Testing Environment – Both of our labs are climate controlled, ensuring accurate drying and analysis—even for high-moisture fuels.
Data You’ll Receive
- Fineness Analysis – Verifies proper grinding and particle distribution.
- Fly Ash LOI (Loss on Ignition) – A direct indicator of unburned carbon and combustion efficiency.
- LOI Breakdown by Size – Composite LOI and LOI on particles passing 200 mesh, helping you pinpoint the root cause of combustion inefficiencies.
Whether you need
on-the-spot analysis during testing or a
deep dive into fuel properties at our lab,
SAS Global delivers the precise data and expert insights you need to drive better combustion performance.